MDFO

Flow measuring orifice with self-sealed measuring points.

Product Information

Flow measuring orifice

Flow measuring orifice with self-sealed measuring points.

Technical description

Application:

Heating and cooling systems
Tapwater systems

Function:

Measuring

Dimensions:

DN 20-900

Pressure class:

PN 16 (DN 20-900)
PN 25 (DN 65-300)
PN 40 (DN 65-450)

Temperature:

Max. working temperature: 120°C
Min. working temperature: -20°C

Material:

Fixed orifice: Stainless steel X3CrNiMo17-13-3 (No. 1.4436 according to EN 10028-7 or EN 10272 (BS 970 316/S16)
Measuring points: AMETAL®
Sealing (measuring points): EPDM

AMETAL® is the dezinfication resistant alloy of TA.

Marking:

TA, MDFO, DN, PN, Charge No, flow direction arrow.
DN 20-150 (PN 16): BS 7350.

Photos

Download all

Drawings

Download all

2D/3D

Download all

Technical Specifications

Installation Instructions

Legal Documents